Quick Specs
- Capacity: 3000 VA / 2400 W
- Frequency Range: 40 Hz ~ 70 Hz
- Battery Type: 12 V / 9 Ah
- Pure Sinewave
- Power cables and cables that are used to connect to other devices are not included and can be bought separately.
This item ships within 2-5 working days from date of order if stock is available. Kindly confirm with our sales team.
Difference between Online UPS and Offline UPS
Quick Specs
- Capacity: 3000 VA / 2400 W
- Frequency Range: 40 Hz ~ 70 Hz
- Battery Type: 12 V / 9 Ah
- Pure Sinewave
- Power cables and cables that are used to connect to other devices are not included and can be bought separately.
Phase
Single phase with ground
Capacity
3000 VA / 2400 W
Input
Voltage Range
Low Line Transfer
160 VAC/140 VAC/120 VAC/110 VAC ± 5% (Ambient Temp. <35°C) (based on load percentage 100% - 80% / 80% - 70% / 70-60% - 0)
Low Line Comeback
175 VAC/155 VAC/135 VAC/125 VAC ± 5% (Ambient Temp. <35°C) (based on load percentage 100% - 80% / 80% - 70% / 70-60% - 0)
High Line Transfer
300 VAC ± 5%
High Line Comeback
290 VAC ± 5%
Frequency Range
40 Hz ~ 70 Hz
Power Factor
≥ 0.99 @ nominal voltage
Output
Output Voltage
200/208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
± 1%
Frequency Range (Synchronised Range)
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Current Crest Ratio
3:1
Harmonic Distortion
≤ 3 % THD (Linear Load), ≤ 6 % THD (non-linear load)
Transfer Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
4ms (Typical)
Waveform (Batt. Mode)
Pure Sinewave
Efficiency
AC Mode
90%
Battery Mode
88%
Battery
Battery Type
12 V / 9 Ah
Numbers
6
Typical Recharge Time
4 hours to recover to 90% capacity
Charging Current (max.)
1.0 A
Charging Voltage
82.1 VDC ± 1%
Indicators
LCD Panel
UPS status, Load level, Battery level, Input/output Voltage, Discharge timer and Fault Conditions
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
Physical
Dimension, D x W x H (mm)
630 x 483 x 88 [2U]
Net Weight (kgs)
29.3
Environment
Humidity
20-90 % RH @ 0-40°C (non-condensing)
Noise Level
Less than 50dB @ 1 Meter
Management
Smart RS-232/USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix and Mac
Optional SNMP