Mecer 10000VA on-line UPS ME-10000-WPTU - Please confirm lead time
Rated 3.5/5 based on 11 customer reviews

Mecer 10000VA on-line UPS ME-10000-WPTU - Please confirm lead time

Availability: on request
R 17,565.22
EXCLUDING VAT
R 20,200.00
INCLUDING VAT


NB: Mobicred will only consider items priced under R35000

Quotes requested

This item ships within 2-5 working days from date of order if stock is available. Kindly confirm with our sales team.

Collection is not possible for this item due to its weight and size - Shipping required from warehouse to destination area.

Difference between Online UPS and Offline UPS

Quick Specs

  • Capacity: 10000 VA / 8000 W
  • Frequency Range: 46~54 Hz or 56~64 Hz
  • Battery Type: 12 V / 9 Ah
  • Pure Sinewave
  • Requires professional installation to electrical distribution board
  • Power cables and cables that are used to connect to other devices are not included and can be bought separately.

This item ships within 2-5 working days from date of order if stock is available. Kindly confirm with our sales team.

Collection is not possible for this item due to its weight and size - Shipping required from warehouse to destination area.

Difference between Online UPS and Offline UPS

Quick Specs

  • Capacity: 10000 VA / 8000 W
  • Frequency Range: 46~54 Hz or 56~64 Hz
  • Battery Type: 12 V / 9 Ah
  • Pure Sinewave
  • Requires professional installation to electrical distribution board
  • Power cables and cables that are used to connect to other devices are not included and can be bought separately.

Capacity
10000 VA / 8000 W

Input
Voltage
208/220/230/240 VAC

Voltage Range
110-300VAC @ 50% Load, 176-300VAC @ 100% load

Frequency Range
46~54 Hz or 56~64 Hz

Power Factor
≥ 0.99 @ nominal voltage (100% load)

Output
Output Voltage
220/230/240 VAC

AC Voltage Regulation (Batt. Mode)
±1%

Frequency Range (Synchronized Range)
46~54 Hz or 56~64 Hz

Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz

Current Crest Ratio
3:1 (max.)

Harmonic Distortion
≤ 3 % THD (Linear Load) ; ≤ 5 % THD (Non-linear Load)

Transfer Time
AC Mode to Batt. Mode
Zero

Inverter to Bypass
Zero

Waveform (Batt. Mode)
Pure Sinewave

Efficiency
AC Mode
93 %

Battery Mode
91%

Battery
Standard Model
Battery Type
12 V / 9 Ah

Numbers
16

Typical Recharge Time
9 hours recover to 90% capacity

Charging Current (max.)
1 A / 2 A

Charging Voltage
218.4 VDC ± 1%

Long-run Model
Battery Type
Depending on the applications running

Numbers
16~20 (Adjustable)

Charging Current (max.)
1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries)

Charging Voltage
218.4 VDC ± 1% (Based on 16pcs Batteries)

Indicators
LCD Display
UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge timer and Fault conditions

Alarm
Battery Mode
Sounding every 4 seconds

Low Battery
Sounding every second

Overload
Sounding every twice second

Fault
Continuously Sounding

Physical
Standard Model
Dimensions, D X W X H(mm)
442  x 190 x 688

Net Weight (kgs)
66

Long-run Model
Dimensions, D X W X H(mm)
442  x 190 x 318

Net Weight (kgs)
16

Environment
Humidity
0-95 % RH @ 0- 40° (non-condensing)

Noise Level
Less than 58dB @ 1 meter

Management
Smart RS-232 and USB
Supports Windows® 2000/2003/XP/Vista/2008. Windows® 7/8, Linus and MAC