Mecer 10000VA 6U on-line Sine Wave Rackmountable UPS ME-10000-WPRU - Please confirm lead time
- Category: Mecer Inverters and UPSs, UPS and Inverters
EXCLUDING VAT
R 22,595.00INCLUDING VAT
NB: Mobicred will only consider items priced under R35000
Quotes requested
This item ships within 2-5 working days from date of order if stock is available. Kindly confirm with our sales team.
Difference between Online UPS and Offline UPS
Quick Specs
- Capacity: 10000 VA / 8000 W
- Frequency Range: 46~54 Hz or 56~64 Hz
- Battery Type: 12 V / 9 Ah
- Pure Sinewave
- Power cables and cables that are used to connect to other devices are not included and can be bought separately.
This item ships within 2-5 working days from date of order if stock is available. Kindly confirm with our sales team.
Difference between Online UPS and Offline UPS
Quick Specs
- Capacity: 10000 VA / 8000 W
- Frequency Range: 46~54 Hz or 56~64 Hz
- Battery Type: 12 V / 9 Ah
- Pure Sinewave
- Power cables and cables that are used to connect to other devices are not included and can be bought separately.
Overview
Mecer 10000VA On-Line Sine Wave 6U Rackmount UPS (ME-10000-WPRU) has a wide input voltage range and an available converter mode.
Features
This UPS can charge up to 90% in battery capacity within a 9 hour period. This UPS is generator compatible and the Waveform is Pure Sinewave.
Note
A UPS is not designed to provide continuous power, it allows a computer or device to keep running for a short period of time when the primary power source is lost.
Phase
Single phase with ground
Capacity
10000 VA / 8000 W
Input
Voltage Range
Low Line Transfer
176 VAC ± 3% @ 100% load, 110 VAC ± 3% 50% load
Low Line Comeback
186 VAC ± 3% @ 100% load, 120 VAC ± 3% 50% load
High Line Transfer
300 VAC ± 3%
High Line Comeback
290 VAC ± 3%
Frequency Range
46~54 Hz or 56~64 Hz
Power Factor
≥ 0.99 @ 100% load
Output
Output Voltage
208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
± 1%
Frequency Range (Synchronised Range)
46 ~ 54 Hz or 56 ~ 64 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1
Harmonic Distortion
≤ 3 % THD (Linear Load), ≤ 5 % THD (non-linear load)
Transfer Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
Zero
Waveform (Batt. Mode)
Pure Sinewave
Efficiency
AC Mode
93%
Battery Mode
81%
Battery
Battery Type
12 V / 9 Ah
Numbers
16
Typical Recharge Time
9 hours to recover to 90% capacity
Charging Current (max.)
1.0 A / 2.0 A (adjustable)
Charging Voltage
218.4 VDC ± 1%
Indicators
LCD Panel
UPS status, Load level, Battery level, Input/output Voltage, Discharge timer and Fault Conditions
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
Physical
Dimension, D x W x H (mm)
UPS: 580 x 483 x 133 [3U]
Battery: 588 x 438 x 133 [3U]
Net Weight (kgs)
UPS: 18
Battery: 51
Environment
Humidity
0-95 % RH @ 0-40°C (non-condensing)
Noise Level
Less than 58dB @ 1 Meter
Management
Smart RS-232/USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix and Mac
Optional SNMP
Power management from SNMP manager and web browser